Applications
These cables are used for electricity supply in low voltage installation system, They are suitable for installation in indoors and outdoors, in cable ducts, under ground, in power and switching stations, local energy distributions, industrial plants, where there is no risk of mechanical damage. The lead sheath brings an enhanced resistance to aromatic hydrocarbons.
Construction
Conductors
The conductors shall be either of Class 1 or Class 2 of plain or metal-coated annealed copper or of plain aluminium or aluminium alloy, or of Class 5 of plain or metal-coated copper in accordance with IEC 60228.
Insulation
XLPE material and thickness shall be as per IEC 60502-1, rated for 90℃ continuous operation.
Colour Code
1 Core | Brown or Blue |
2 Cores | Brown, Blue |
3 Cores | Brown, Black, Grey |
4 Cores | Blue, Brown, Black, Grey |
5 Cores | Green/Yellow, Blue, Brown, Black, Grey |
Above 5 Cores | Black Cores with White numerals |
Other colours can be manufactured upon request.
Assembly / Inner Covering
The inner coverings may be extruded or lapped. For cables with circular cores, except cables with more than five cores, a lapped inner covering shall be permitted only if the interstices between the cores are substantially filled. A suitable binder is permitted before application of an extruded inner covering. The material is compatible with the insulating material,The materials used for inner coverings and fillers shall be suitable for the operating temperature of the cable and compatible with the insulating material.For halogen free cables, the inner covering and fillers shall also be halogen free compound.
Optional : Lead Sheath
lead or lead alloy and shall be applied as a reasonably tight-fitting seamless tube.
Optional : Seperation Sheath
The seperation sheath shall be of extruded PVC Type ST2 as per IEC 60502-1, or other material refer to outer sheath material.
Optional: Armour
Aluminum/galvanized steel/steel wires applied helically over the Inner Covering as per IEC 60502-1, or double aluminum/steel tapes and copper/tinned copper wire can also be manufactured upon request.
Outer Sheath
Outer sheath shall be of extruded PVC Type ST1/ST2 as per IEC 60502-1, Polyethylene type ST3/ST7, Halogen free compound ST8, Polychloroprene, chlorosulfonated polyethylene or similar polymers, type SE1 are also available on request.
Optional : Fire Performance of Cable Sheaths
Cables can be supplied with special flame retardant PVC outer sheath to comply with the flame test requirements of IEC 60332-3-22, IEC 60332-3-23 and IEC 60332-3-24, Halogen Free material comply to IEC60754-1/2 and IEC 60684-2.
The sizes to any recognized standards or customer specification can also be supplied as per customer's requirements.
Voltage rating for XLPEPower Cable | No. x Nominal Cross Section of Conductor No. x mm2 | |||||||
1 core | 2 core | 3 core | 3+1 core | 4core | 3+2 core | 4+1 core | 5 core | |
0.6/1 kV | 1x4 mm2 | 2x4 mm2 | 3x4 mm2 | 3x4 mm2 + 1x2.5mm2 | 4x4 mm2 | 3x4 mm2 + 2x2.5mm2 | 4x4 mm2 + 1x2.5mm2 | 5x2.5 mm2 |
1x6 mm2 | 2x6 mm2 | 3x6 mm2 | 3x6 mm2 + 1x4 mm2 | 4x6 mm2 | 3x6 mm2 + 2x4 mm2 | 4x6 mm2 + 1x4 mm2 | 5x4 mm2 | |
1x10 mm2 | 2x10 mm2 | 3x10 mm2 | 3x10 mm2 + 1x6 mm2 | 4x10 mm2 | 3x10 mm2 + 2x6 mm2 | 4x10 mm2 + 1x6 mm2 | 5x6 mm2 | |
1x16 mm2 | 2x16 mm2 | 3x16mm2 | 3x16 mm2 + 1x10 mm2 | 4x16 mm2 | 3x16 mm2 + 2x10 mm2 | 4x16 mm2 + 1x10 mm2 | 5x10 mm2 | |
1x 25 mm2 | 2x 25 mm2 | 3x 25 mm2 | 3x25 mm2 + 1x16mm2 | 4x25 mm2 | 3x25 mm2 + 2x16mm2 | 4x25 mm2 + 1x16mm2 | 5x16 mm2 | |
1x35 mm2 | 2x35 mm2 | 3x 35 mm2 | 3x35 mm2 + 1x16mm2 | 4x35 mm2 | 3x35 mm2 + 2x16mm2 | 4x35 mm2 + 1x16mm2 | 5x25 mm2 | |
1x50 mm2 | 2x50 mm2 | 3x 50 mm2 | 3x50 mm2 + 1x25mm2 | 4x50 mm2 | 3x50 mm2 + 2x25mm2 | 4x50 mm2 + 1x25mm2 | 5x35 mm2 | |
1x70 mm2 | 2x70 mm2 | 3x 70 mm2 | 3x70 mm2 + 1x35mm2 | 4x70 mm2 | 3x70 mm2 + 2x35mm2 | 4x70 mm2 + 1x35mm2 | 5x50 mm2 | |
1x95 mm2 | 2x95 mm2 | 3x 95 mm2 | 3x95 mm2 + 1x50mm2 | 4x95 mm2 | 3x95 mm2 + 2x50mm2 | 4x95 mm2 + 1x50mm2 | 5x70 mm2 | |
1x120 mm2 | 2x120 mm2 | 3x 120 mm2 | 3x120mm2 + 1x70mm2 | 4x120 mm2 | 3x120mm2 + 2x70mm2 | 4x120mm2 + 1x70mm2 | 5x95 mm2 | |
1x150 mm2 | 2x150 mm2 | 3x 150 mm2 | 3x150mm2 + 1x70mm2 | 4x150 mm2 | 3x150mm2 + 2x70mm2 | 4x150mm2 + 1x70mm2 | ||
1x185 mm2 | 2x185 mm2 | 3x 185 mm2 | 3x185mm2 + 1x95mm2 | 4x185 mm2 | 3x185mm2 + 2x95mm2 | 4x185mm2 + 1x95mm2 | ||
1x240 mm2 | 3x 240 mm2 | 3x240mm2 + 1x120mm2 | 4x240 mm2 | 3x240mm2 + 2x120mm2 | 4x240mm2 + 1x120mm2 | |||
1x300 mm2 | 3x 300 mm2 | 3x300mm2 + 1x150mm2 | 4x300 mm2 | 3x300mm2 + 2x150mm2 | 4x300mm2 + 1x150mm2 | |||
1x400 mm2 | ||||||||
1x500 mm2 |
Parameter/Data Sheet
Please click or download below ACAR pdf to check the parameter regard toIEC60502-1 BS5467 BS6346 BS6724 BS8573 standards.
BS_8573_Five_Core_600_1000V_XLPE_Insulation_LSZH_Sheath_Cables_to_BS_8573.pdf
BS_8573_Single_Core_600_1000V_XLPE_Insulation_LSZH_Sheath_Cables.pdf
BS_8573_Four_Core_600_1000V_XLPE_Insulation_LSZH_Sheath_Cables_to_BS 8573.pdf
BS_8573_Three_Core_600_1000V_XLPE_Insulation_LSZH_Sheath_Cables_to_BS_8573.pdf
BS_8573_Two_Core_600_1000V_XLPE_Insulation_LSZH_Sheath_Cables.pdf
IEC_60502-1_600_1000V_XLPE_Insulated_Cables.pdf
IEC_60502-1_600_1000V_XLPE_Insulated_Lead_Sheathed_Cables.pdf
Type | Designation | Main Applications |
YJV YJLV | Copper(Aluminium)Conducter XLPE Insulated PVC Sheathed Power Cable | For laying indoor and outdoor tunnels, able to bear a centain traction installation, but unable to bear pulling force and pressure, single core cable can not be laid in the magnetic tube. Flame retardant, fire-resistant cable suitable for the places with higher requirements for fire protection. |
ZR-YJV ZA-YJV ZB-YJV ZC-YJV ZR-YJLV ZA-YJLV ZB-YJLV ZC-YJLV | Copper(Aluminium)Conducter Flame Retardant XLPE Insulated PVC Sheathed Power Cable | |
NH-YJV NHZA-YJV NHZB-YJV NHZB-YJV NHZC-YJV | Copper(Aluminium)Conducter Fire-resistant XLPE Insulated PVC Sheathed Power Cable | |
YJV22 YJLV22 | Copper(Aluminium)Conducter XLPE Insulated Steel Tape Armoured PVC Sheathed Power Cable | For laying direct in ground, able to bear a centain traction installation, pulling force and pressure, flame retardant, fire-resistant cable suitable for the place with higher requirements for fire protection. |
ZR-YJV22 ZA-YJV22 ZB-YJV22 ZC-YJV22 ZR-YJLV22 ZA-YJLV22 ZB-YJLV22 | Copper(Aluminium)Conducter Flame Retardant XLPE Insulated Steel Tape Armoured PVC Sheathed Power Cable | |
ZC-YJLV22 NH-YJV22 NHZA-YJV22 NHZB-YJV22 NHZB-YJV22 NHZC-YJV22 | Copper(Aluminium)Conducter Fire-resistant XLPE Insulated Steel Tape Armoured PVC Sheathed Power Cable |
Type | No. of Cores | Nom. Cross-section of Conductor(mm²) | |
Copper Core | Aluminum Core | ||
1 Core | 1.5-630 | 2.5-630 | |
YJV YJLV ZR-YJV ZA-YJV ZB-YJV ZC-YJV | 2 Cores | 1.5-400 | 2.5-400 |
ZR-YJLV ZA-YJLV ZB-YJLV ZC-YJLV NH-YJV | 3 Cores | ||
NHZA-YJV NHZB-YJV NHZC-YJV YJV22 YJLV22 | 4 Cores | ||
ZR-YJV22 ZA-YJV22 ZB-YJV22 ZC-YJV22 | 5 Cores | ||
ZR-YJLV22 ZA-YJLV22 ZB-YJLV22 ZC-YJLV22 | 3+1 Cores | ||
NH-YJV22 NHZA-YJV22 NHZB-YJV22 NHZC-YJV22 | 3+2 Cores | ||
4+1 Cores |
More
Matching Products
- CU/AL 0.6/1KV 1.8/3KV 1-5 Core YJV YJLV YJV22 YJV32 LV Power Cable
- Three Core Medium Voltage Power Cable
- Building Wire
*Describe Your Buying Requirements in Detail